Two Winding Transformers 2021
Electrical parameters of two winding transformers in all licence areas.
Data Dictionary
Title | Type | Label | Description | Example |
---|---|---|---|---|
Area | text | Licence area for data |
EMIDS | |
GSP Group | text | GSP Group |
Berkswell 132kV | |
Node 1 | text | Busbar code at the higher voltage end of the transformer |
COVC1J | |
Operating Voltage 1 | numeric | kV | Operating Voltage 1 |
132 |
Node 2 | text | Busbar code at the Lower voltage end of the transformer |
COVC3 X | |
Operating Voltage 2 | numeric | kV | Operating Voltage 2 |
33 |
Status | text | kV | New, Removed or Unchanged |
New |
Vector Group | text | Transformer vector group |
xd1 | |
R1 | numeric | % on 100MVA base | Positive Sequence Resistance |
0.503 |
X1 | numeric | % on 100MVA base | Positive Sequence Reactance |
18.666 |
X0 | numeric | % on 100MVA base | Zero Sequence Reactance |
15.87 |
Min Tap % | numeric | % | Minimum Tap Range |
-20 |
Max Tap % | numeric | % | Maximum Tap Range |
10 |
Nominal Rating | numeric | MVA | Rating |
120 |
Emergency Rating | numeric | MVA | Rating |
156 |
Reverse Power Capability | text | MVA where Numeric | Full, Partial or MVA |
|
Method of Earthing | text | Method of Earthing |
Solid/ET+NER |