Title Type Label Description Example
Licence text -

Licence area for data

SWEST
GSP Group text -

nan

Bishops Wood 132kV
Node 1 text -

Busbar code at the higher voltage end of the transformer

KIDD 1
Operating Voltage 1 numeric kV

nan

132
Node 2 text -

Busbar code at one of the two Lower voltage ends of the transformer

KIDD51_LV1
Operating Voltage 2 numeric kV

nan

11
Node 3 text -

Busbar code at one of the two Lower voltage ends of the transformer

KIDD51_LV2
Operating Voltage 3 numeric kV

nan

11
Status text -

New, Removed or Unchanged

New
Vector Group text -

Transformer vector group

YN d1 d1
R1 numeric % on 100MVA Base

Positive Sequence Resistance

1.12
X1 HV-LV numeric % on 100MVA Base

Positive Sequence Reactance

50.5
X1 LV-Tertiary numeric % on 100MVA Base

Positive Sequence Reactance

26.8
X1 HV-Tertiary numeric % on 100MVA Base

Positive Sequence Reactance

26.73
X0 HV-LV text % on 100MVA Base

Zero Sequence Reactance

50.51
X0 LV-Tertiary text % on 100MVA Base

Zero Sequence Reactance

175.89
X0 HV-Tertiary text % on 100MVA Base

Zero Sequence Reactance

49.01
Min Tap numeric %

Minimum Tap Range

-20
Max Tap numeric %

Maximum Tap Range

10
Nominal Rating numeric MVA

Nominal Rating of the transformer

20
Emergency Rating text MVA

Forced / Emergency Rating of the transformer

40
Reverse Power Capability text MVA where Numeric

Full, Partial or MVA

Full
Method of Earthing text -

nan

TR