Title Type Label Description Example
Network_Reference_ID numeric

Network reference ID of the substation associated with this site.

314897
Parent_Network_Reference_ID numeric

Network reference ID of the 'parent' (higher voltage level) substation associated with this site.

314785
Substation_Name text text

Substation Site Name

Alderton 66/11kv
Substation_Number numeric

Substation Network Reference

670088
Asset_Type text text

Type of asset

Primary
Latitude numeric degrees

Grid co-ordinates (Latitude)

51.9913
Longitude numeric degrees

Grid co-ordinates (Longitude)

-1.9982
Fault_Level_Headroom text MVA

Fault level headroom of Super Grid Point (from National Grid via Statement of Works Appendix G)

4.291
Group text text

Name of the Grid Supply Point the substation ultimately connects to.

Port Ham 132kV
Bulk_Supply_Point_Name text text

Name of the bulk supply substation which transforms voltage from 132kV (or 66kV at Feckenham) to 66kV, 33kV or 11kV. If no Primary substation is listed, this is the substation in question.

Cheltenham 132 66
Primary_Substation text text

Name of the Primary substation which transforms voltage between the Bulk Supply Point and 11kV or 6.6kV distribution substations.

Alderton 66 11
Upstream_Voltage numeric kV

Highest voltage level at the substation

66
Downstream_Voltage numeric kV

Lowest voltage level at the substation

11
Firm_Capacity_of_Substation_(MVA) numeric MVA

Firm demand capacity of the substation

13
Reverse_Power_Capability_(MVA) numeric MVA

Reverse power capability of substation taken as 50% of the substation emergency rating.

6.5
Measured_Peak_Demand_(MVA) numeric MVA

Measured substation peak demand in the previous financial year

7.36
Upstream_Equipment_Ratings_3Ph_Make_(kA) numeric kA

Fault rating of HV switchgear for 3ph faults (make)

21.87
Upstream_Equipment_Ratings_3Ph_Break_(kA) numeric kA

Fault rating of HV switchgear for 3ph faults break)

8.75
Upstream_Short_Circuit_Currents_3Ph_Make_(kA) numeric kA

Fault level at HV side of the substation for 3ph faults (make)

7.09
Upstream_Short_Circuit_Currents_3Ph_Break_(kA) numeric kA

Fault level at HV side of the substation for 3ph faults (break)

3.07
Downstream_Equipment_Ratings_3Ph_Make_(kA) numeric kA

Fault rating of LV switchgear for 3ph faults (make)

32.8
Downstream_Equipment_Ratings_3Ph_Break_(kA) numeric kA

Fault rating of LV switchgear for 3ph faults break)

13.1
Downstream_Short_Circuit_Currents_3Ph_Make_(kA) numeric kA

Fault level at LV side of the substation for 3ph faults (make)

10.8
Downstream_Short_Circuit_Currents_3Ph_Break_(kA) numeric kA

Fault level at LV side of the substation for 3ph faults (break)

4.03
Upstream_Equipment_Ratings_1Ph_Make_(kA) numeric kA

Fault rating of HV switchgear for 1ph faults (make)

78.75
Upstream_Equipment_Ratings_1Ph_Break_(kA) numeric kA

Fault rating of HV switchgear for 1ph faults break)

31.5
Upstream_Short_Circuit_Currents_1Ph_Make_(kA) numeric kA

Fault level at HV side of the substation for 1ph faults (make)

0.95
Upstream_Short_Circuit_Currents_1Ph_Break_(kA) numeric kA

Fault level at HV side of the substation for 1ph faults (break)

0.62
Downstream_Equipment_Ratings_1Ph_Make_(kA) text kA

Fault rating of LV switchgear for 1ph faults (make)

78.75
Downstream_Equipment_Ratings_1Ph_Break_(kA) text kA

Fault rating of LV switchgear for 1ph faults break)

31.5
Downstream_Short_Circuit_Currents_1Ph_Make_(kA) numeric kA

Fault level at LV side of the substation for 1ph faults (make)

2.64
Downstream_Short_Circuit_Currents_1Ph_Break_(kA) numeric kA

Fault level at LV side of the substation for 1ph faults (break)

0.96
Demand_Headroom_(MVA) numeric MVA

Demand Headroom is calculated from substation firm capacity minus peak demand

5.64
Generation_Headroom_(MVA) numeric MVA

Generation headroom is calculated from substation reverse power capacity minus total inferred generation

-1.71
Fault_Level_Headroom_(kA) numeric kA

Fault Level Headroom is calculated from the HV or LV switchgear with the highest 3ph or 1ph short-circuit duty

5.68
Total_Inferred_Generation_(MVA) numeric MVA 9.9146
Demand_Headroom_RAG text Red/Amber/Green

Demand connection potential indicator of substation. Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Green
Generation_Headroom_RAG text Red/Amber/Green

Generation connection potential indicator of substation. Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Red
Fault_Level_Headroom_RAG text Red/Amber/Green

Fault level issue indicator of substation. Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Green
Aggregated_Demand_Headroom_RAG text Red/Amber/Green

Demand connection potential indicator of substation (taking parent substation in to account). Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Green
Aggregated_Generation_Headroom_RAG text Red/Amber/Green

Generation connection potential indicator of substation (taking parent substation in to account). Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Red
Upstream_Demand_Headroom_RAG text Red/Amber/Green

Demand connection potential indicator of parent substation. Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Green
Upstream_Generation_Headroom_RAG text Red/Amber/Green

Generation connection potential indicator of parent substation. Red (< 10% of capacity remaining), Amber (≥ 10% and < 25% of capacity remaining), Green (≥ 25% of capacity remaining)

Green
Upstream_Demand_Headroom numeric MVA

Maximum demand capacity available at the Bulk Supply Point

30.03
Upstream_Generation_Headroom numeric MVA

Maximum generation capacity available at the Bulk Supply Point

4.78
Generator_Types text text

Types of generator connected at substation

Storage (Battery),Photovoltaic
Generation_Connected_(kVA) numeric kVA

Sum of installed generation capacity connected at substation

14743.8
Generation_Offered_Not_Accepted_(kVA) numeric kVA

Sum of kVA of generation firm quotes offered at the substation, but not yet accepted.

0
Generation_Accepted_Not_Connected_(kVA) numeric kVA

Sum of kVA of generation firm quotes with accepted offers, but not yet connected.

15000
Statement_of_Works text

Statement of Works text with reference to the Grid Supply Point.

In order to allow WPD to contain voltage within acceptable limits at the National Electricity Transmission System (NETS) / Distribution System interface, the Customer must ensure that the generators (>=1MW) have the capability to operate between 0.95 leading and 0.95 lagging power factor. Customers will be advised of the target Power Factor within this range. ------- National Grid Electricity Transmission (NGET) has instructed that WPD shall maintain a facility such that under emergency conditions on the National Electricity Transmission System (NETS), WPD shall have the ability to de-energise embedded generation (>=1MW) upon instruction from NGET. ------- WPD has previously submitted a Statement of Works (SoW) request to National Grid Electricity Transmission (NGET) for other generation schemes at Port Ham GSP. This process has highlighted that thermal generation and/or storage will be prevented from connection until further works are completed. The assessment of these further works may require WPD to make a new Project Progression application to NGET. ------- In order to allow WPD to contain voltage within acceptable limits at the National Electricity Transmission System (NETS) / Distribution System interface, the Customer must ensure that the generators (>=1MW) have the capability to operate between 0.95 leading and 0.95 lagging power factor. Customers will be advised of the target Power Factor within this range. ------- National Grid Electricity Transmission (NGET) has instructed that WPD shall maintain a facility such that under emergency conditions on the National Electricity Transmission System (NETS), WPD shall have the ability to de-energise embedded generation (>=1MW) upon instruction from NGET. ------- WPD has previously submitted a Statement of Works (SoW) request to National Grid Electricity Transmission (NGET) for other generation schemes at Port Ham GSP. This process has highlighted that thermal generation and/or storage will be prevented from connection until further works are completed. The assessment of these further works may require WPD to make a new Project Progression application to NGET.