Fault Level 2020
Dataset description:
Fault level data encompassing system impedance, calculated fault levels and ratings.
Source: Fault Level
Data Dictionary
Title | Type | Label | Description | Example |
---|---|---|---|---|
Area | text | nan | Licence area for data |
EMIDS |
GSP Group | text | nan | Grid Supply Point |
Berkswell |
Name | text | nan | Substation or Busbar name |
Coventry Central 132kV |
Node | text | nan | Unique node ID |
COVC1J |
Voltage | numeric | kV | Busbar voltage |
132 |
System Resistance | numeric | Ohms (p.u on 100MVA base) | System resistance at busbar |
0.06738 |
System Reactance | numeric | Ohms (p.u on 100MVA base) | System reactance at busbar |
0.62116 |
Three Phase Peak Make Fault Current | numeric | kA | Calculated Three Phase Peak Make Fault Current |
21.03 |
Single Phase Peak Make Current | numeric | kA | Calculated Single Phase Peak Make Current |
2.11 |
Three Phase RMS Break Fault Current | numeric | kA | Calculated Three Phase RMS Break Fault Current |
8.09 |
Single Phase RMS Break Fault Current | numeric | kA | Calculated Single Phase RMS Break Fault Current |
1.47 |
Three Phase Peak Make Rating | numeric | kA | Switchgear Three Phase Peak Make Rating |
32.81 |
Single Phase Peak Make Rating | numeric | kA | Switchgear Single Phase Peak Make Rating |
45.9 |
Three Phase RMS Break Rating | numeric | kA | Switchgear Three Phase RMS Break Rating |
15.3 |
Single Phase RMS Break Rating | text | kA | Switchgear Single Phase RMS Break Rating |
18.4 |